From Wikipedia, the free encyclopedia

A firestop or fire-stopping is a form of passive fire protection that is used to seal around openings and between joints in a fire-resistance-rated wall or floor assembly. Firestops are designed to maintain the fire-resistance rating of a wall or floor assembly intended to impede the spread of fire and smoke.[1]

YouTube Encyclopedic

  • 1/5
    Views:
    25 100
    9 815
    77 746
    11 880
    2 835
  • StoveTop FireStop featured on KCAL-TV Los Angeles
  • StoveTop FireStop Product Demonstrations
  • StoveTop FireStop Microhood Demonstration
  • IFC Inspecting Firestop for Compliance
  • Firestop Sleeve Kit - STI Ready Sleeve

Transcription

Description

Firestops prevent unprotected horizontal and vertical penetrations in a fire-resistance-rated wall or floor assembly from creating a route by which fire and smoke can spread that would otherwise have been fire resisting construction, e.g. where a pipe passes through a firewall.

Fire stopping is also to seal around gaps between fire resisting constructions, e.g. the linear gap between a wall and the floor above, in order for construction to form a complete barrier to fire and smoke spread.

Opening types

Firestops are used in:

  • Electrical, mechanical, and structural penetrations
  • Unpenetrated openings (such as openings for future use)
  • Re-entries of existing firestops
  • Control or sway joints in fire-resistance-rated wall or floor assemblies
  • Junctions between fire-resistance-rated wall or floor assemblies
  • Head-of-wall (HOW) joints, where non-load-bearing wall assemblies meet floor assemblies

Numeric characters are used to identify what penetrant, if any, can be found within the present system and help identify what UL-tested system was used.

Classification for penetrations and the barriers they penetrate, are categorized by a standardized letter-number system that has been adopted by all firestop products manufacturers.[2][3] A typical system would consist of several letters, followed by a series of numbers indicating the type of penetrant that is passing through the particular barrier ex: (FB-5533.)

Materials

Components include intumescents, cementitious mortars, silicone, firestop pillows, mineral fibers, and rubber compounds.

Maintenance

Firestops should be maintained in accordance with the certification listing. Construction documentation sometimes includes an inventory of all firestops in a building, with drawings indicating their location and certification listings. Using this, a building owner can meet the fire code relating to fire barriers. Improper repairs may otherwise result, which would violate the fire code and could allow a fire to travel between areas intended by code to be separated during a fire.

Ratings

Firestop materials are not rated per se. They receive a fire rating by combining materials in an arrangement specific to the item (a pipe or cable, for example) penetrating the fire-rated wall or floor and the construction arrangement of the fire-rated wall or floor. A two-hour-rated pipe-penetration firestop may consist of a layer of caulking over packed mineral wool. The arrangement, not the caulking, provides the two-hour rating. The individual firestop materials and the overall firestop assembly are listed.

Testing and certification

Certification listings include those available from:

FIRAS scheme- Warrington Fire (UK)

Regulations and compliance

When the installed configuration does not comply with the appropriate certification listing, the fire-resistance rating may be lower than expected. Each opening in a fire-resistance-rated wall or floor in a building must have a certification listing. There are thousands of listings from various certification and testing laboratories. The Canadian and United States Underwriters Laboratories publish books listing firestop manufacturers who have contracted with them for testing and certification.

Inadequate firestopping

No firestopping

Older buildings often lack firestops. A thorough inspection can identify all vertical and horizontal fire barriers and their fire ratings, and all breaches in these barriers (which can be sealed with approved methods).

Non-listed attempts

Firestops created by contractors or building maintenance personnel which are not listed are not credited with an adequate fire resistance rating for building-code compliance purposes. They are usually short-term, cost-cutting measures at the expense of fire safety and code compliance. One common error is citing a listing for a product which may be for another use. An insulation with an active listing of a certain flame-spread rating is unacceptable for firestopping purposes.

See also

References

  1. ^ "Fire Stopping: What Every Contractor Needs to Know | EC Mag". www.ecmag.com. Archived from the original on 2017-09-07. Retrieved 2017-09-06.
  2. ^ "3M Technical Library/Technical Bulletins". 3M.
  3. ^ "Firestop Contractors International Association Technical-Resources". fcia.com.
  4. ^ http://www.fmglobal.com/assets/pdf/fmapprovals/4991.pdf Approval Standard for Approval of Firestop Contractors, Class Number 4991

External links

This page was last edited on 1 April 2024, at 20:33
Basis of this page is in Wikipedia. Text is available under the CC BY-SA 3.0 Unported License. Non-text media are available under their specified licenses. Wikipedia® is a registered trademark of the Wikimedia Foundation, Inc. WIKI 2 is an independent company and has no affiliation with Wikimedia Foundation.