Double check valve

From Wikipedia, the free encyclopedia

Double check valve during normal operation
Double check valve during normal operation
Double check valve during reverse flow
Double check valve during reverse flow

A double check valve or double check assembly (DCA) is a backflow prevention device designed to protect water supplies from contamination.[1] It is different from the two-way check valves (sometimes erroneously referred to as double check valves) used in air brake systems on heavy trucks which select from the highest pressure source.

It consists of two check valves assembled in series.[2] This employs two operating principles: firstly one check valve will still act, even if the other is jammed wide open. Secondly the closure of one valve reduces the pressure differential across the other, allowing a more reliable seal and avoiding even minor leakage.

Small valves may be so compact as to be barely noticeable particularly when they are integrated into the bodies of existing taps (faucets). Larger check valves may be installed with ball valves at the ends, for isolation and testing. Often, test cocks (very small ball valves) are in place to attach test equipment for evaluating whether the double check assembly is still functional.

The double check valve assembly is suitable for prevention of back pressure and back siphonage, but is not suitable for high hazard applications. It is commonly used on lawn irrigation, fire sprinkler[2] and combi-boiler systems.[3] If the hazard is higher, even a relatively low hazard such as using antifreeze in the fire sprinkler system, then a more reliable check valve such as a reduced pressure zone device may be mandated.

YouTube Encyclopedic

  • 1/5
    Views:
    3 165
    35 142
    41 469
    23 769
    59 228
  • Floguard Double Check Valve - Product Spotlight
  • Water quality in your home - single and double check valves
  • Plumbing Backflow Preventers
  • Double Check Valve Assembly
  • Water Distribution | Backflow Prevention

Transcription

Dual check valve

A dual check backflow preventer is similar to a double check valve in operation. It has two independent spring-loaded check valves. However, dual check valves usually do not include shutoff valves, may or may not be equipped with test cocks or ports, and is generally less reliable than a double check valve.[4]

See also

References

  1. ^ Dietmar Findeisen (2005) Ölhydraulik: Handbuch für die hydrostatische Leistungsübertragung in der Fluidtechnik; 5. Auflage; Springer Verlag; [[Spezial:ISBN Suche/9783540238805|ISBN 978-3-540-23880-5]]; Seite 637; Online
  2. ^ a b "Double Check Detector Assembly article, portlandoregon.gov". portlandoregon.gov. Retrieved 2024-03-26.
  3. ^ "ASHRAE Terminology". xp20.ashrae.org. ASHRAE Technical Committee. Retrieved 2022-07-27.
  4. ^ "Cross Connection Control and Backflow Prevention Program | Florida Department of Environmental Protection". floridadep.gov. Retrieved 2021-05-16.


This page was last edited on 26 March 2024, at 20:52
Basis of this page is in Wikipedia. Text is available under the CC BY-SA 3.0 Unported License. Non-text media are available under their specified licenses. Wikipedia® is a registered trademark of the Wikimedia Foundation, Inc. WIKI 2 is an independent company and has no affiliation with Wikimedia Foundation.